跳过导航链接
Vault & underground mounting AMDT

  • Execution standard
  • Model
  • Performance
  • Parameters
  • Appearance
  • Null
  • Null
  • Null
  • Technical parameters of DBH15/10 series of embedded non-crystallized alloy transformer
    Rated volume(kVA) Voltage combination Conn. Symb No. No-load loss (W) On-load loss (W) Excit. Curr (%) Impedance (%) Ontology outline dime
    L×W×H (mm)
    Weight (kg)
    High voltage (kV) Tap change (%) Low voltage (kV)
    30 6
    6.3
    6.6
    10
    10.5
    11
    ±2×2.5% ±5% 0.4 Dyn11 33 630 1.5 4 1000×600×850 450
    50 43 910 1.2 4 1050×600×950 550
    63 50 1090 1.1 4 1050×600×1000 700
    80 60 1310 0.9 4 1100×710×1000 700
    100 75 1580 0.8 4 1150×710×1050 800
    125 85 1890 0.6 4 250×750×1000 850
    160 100 2310 0.6 4 1350×800×1050 1150
    200 120 2730 0.6 4 1150×1050×1000 1300
    250 140 3200 0.6 4 1350×1100×1070 1470
    315 170 3830 0.5 4 1400×1100×1150 1760
    400 200 4520 0.5 4 1450×1150×1200 1900
    500 240 5410 0.5 4 1720×1300×1420 2300
  • Null
No.218, Wusong Road, Shanghai, China [sales headquarters] 200080 400-080-1921
F12, Shanghai Baokuang International BM Building
Address: No.666, Zhangwengmiao Road, Fengxian District, Shanghai Postal code:201400
Switchboard: 86-21-68866111 Fax:86-21-68860333
©2013 Shanghai Transformer Work Co., Ltd.